Чим ми можемо вам допомогти сьогодні?
How to program XB4R/XB5R wireless receivers?
1. What you need to know
Programming a Harmony XB5R or XB4R wireless pushbutton has three stages. First set the receiver in pairing mode by pressing the selection button for three seconds. Then select the output on which you want to pair the push button by pressing on the selection button and validate your choice by pressing on the validation button. Then push three times on the pushbutton for teaching it in the receiver; once done the signal LED lights on green steady for two seconds. A ZBRRA receiver holds up to 32 transmitter IDs across its two outputs, the teaching sequence must be completed within 1 minute 30 seconds, and the output becomes active 4 seconds after teaching ends. Full sequences are in instruction sheet S1A57202 and user guide EIO0000000812.
Note : the pairing procedure described in the video is still valid with the current version of receivers.
2. What you are actually configuring
The output function decides what the receiver does when it catches a taught transmitter; it is set per output, not per transmitter. The column that matters most in practice is the third one from the right: some function changes silently erase the IDs already taught to that output, which is the single most common reason a working installation stops responding after a change.
- The output function is set per output, not per transmitter.
- Switching an output to or from start/stop erases the IDs already taught to it; monostable ↔ bistable keeps them. This is the most common reason a working installation stops responding after a change.
- Range is about 100 m in free field, about 25 m with the transmitter in an XALD box and the receiver in a metal enclosure, about 40 m with a ZBRA1 relay antenna.
- Current approach is a ZBRT1 transmitter with a standard XB4/XB5 head;
- Documentation: S1A57202 (receiver sequences), EIO0000000812 (full XB5R reference), S1A57198 (transmitter), S1A57194 (relay antenna).
3. Output function comparison
| Output function | Behaviour | Transmitters | Effect of changing to or from it | Available on |
|---|---|---|---|---|
| Monostable (default) | Momentary - the output follows the press and does not latch | 1 | Switching to or from bistable keeps every taught ID | ZBRRA, ZBRRC |
| Bistable | Alternating - one press latches the output on, the next releases it | 1 | Switching to or from monostable keeps every taught ID | ZBRRA |
| Enable/Disable (standard) | One transmitter energises the output, a second de-energises it; stop has no priority over start | 2 | Switching to or from Enable/Disable clears every ID taught to that output | ZBRRA only |
| Enable/Disable (advanced) | After stop, start is inhibited until a reset transmitter is pressed | 2 + reset | Switching to or from Enable/Disable clears every ID taught to that output | ZBRRA only |
4. Schneider Electric references
| Function | Reference | Product description |
|---|---|---|
| Complete pushbutton | ZB5RTA4 | Red flush wireless and battery less pushbutton, plastic |
| Transmitter | ZBRT1 | Wireless, batteryless transmitter. Current approach: fits under a standard Harmony XB4 or XB5 head. |
| Head | ZB5AA4 | ⌀22 red flush pushbutton head, plastic bezel, spring return. Any standard XB4/XB5 head works. |
| Fixing collar | ZB5AZ009 | Body and fixing collar used to assemble a standard head onto a ZBRT1 (ZB4BZ009 for metal XB4). |
| Receiver - Relays | ZBRRA | Configurable receiver, 2 changeover relay outputs 3 A, 24-240 V AC/DC. Monostable, bistable and enable/disable. Up to 32 transmitter IDs. |
| Receiver -PNP | ZBRRC | Configurable receiver, 4 PNP outputs 200 mA, 24 V DC. Monostable only. |
| Antenna | ZBRA1 | Relay antenna with 5 m cable, extends range to about 40 m in metal enclosures (ZBRA3 for passive through-wall). |
| Enclosure | ZBRM22 | Plastic enclosure with 2 cut-outs for mobile or fixed mounting (ZBRM01 for 1 cut-out). |
Note : Download the instruction sheet from the product page on se.com, browse the current wireless offer in DigiCat, or contact Schneider Electric technical support to validate a layout before installation.
Explore the Explore Industrial Wireless Remote Control page product range on Schneider Electric's website to select the most suitable solution for your application. If you need assistance verifying compatibility with your control scheme, please contact Schneider Electric Technical Support.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.