PowerChute is flagged a vulnerable to CVE-2026-49844
Issue:
PowerChute is flagged a vulnerable to CVE-2026-49844
Product:
PowerChute Serial Shutdown 1.5, 1.6
PowerChute Network Shutdown 5.2
Environment:
All supported operating systems.
Cause:
PowerChute Serial Shutdown 1.5 and 1.6 ship with Log4j versions less than version 2.25.5
PowerChute Network Shutdown 5.2 ships with Log4j versions less than version 2.25.5
Solution:
For PowerChute Serial Shutdown 1.5, 1.6 on Windows:
- Download the attached file PCSS_Log4j_Update.zip file
- Uncompress the file PCSS_Log4j_Update.zip
- Open a command prompt as an administrator
- Change directory to the PCSS_Log4j_Update.zip directory that was created when the zip file PCSS_Log4j_Update.zip was uncompressed.
- Run the command run_patch.cmd
The patch will remove the current log4j files and replace them with log4j version 2.26.1.
For PowerChute Network Shutdown 5.2 on Windows:
- Download the attached file PCNS5.2_log4j_update.zip file
- Uncompress the file PCNS5.2_log4j_update.zip
- Open a command prompt as an administrator
- Change directory to the PCSS5.2_log4j_update directory that was created when the zip file PCSS5.2_log4j_update.zip was uncompressed.
- Run the command run_patch.cmd
The patch will remove the current log4j files and replace them with log4j version 2.26.1.
For PowerChute Network Shutdown version 5.2 on Linux
- Download the attached log4j-2.26.1.tar file, and if needed, copy the file to the Linux system.
- Uncompress the log4j-2.26.1.tar file. The command is tar -xvf log4j-2.26.1.tar.
- Stop the PowerChute service. The command is systemctl stop PowerChute
- Change directory to the PowerChute lib directory. The default path is /opt/APC/PowerChute/group1/lib
- Move the log4j2 files to the APC directory. If PowerChute resides in the default path, the command is mv /opt/APC/PowerChute/group1/lib/log4j2* /opt/APC
- Change directory to the log4j-2.26.1 directory that was created when you uncompressed the tar file.
- Copy the log4j-api-2.26.1jar, log4j-core-2.26.1.jar, log4j-slf4j-impl-2.26.1.jar to the PowerChute lib directory that resides where PowerChute resides. If PowerChute resides in the default path, the command is cp log4j2* /opt/APC/PowerChute/group1/lib
- Start the PowerChute service. The command is systemctl start PowerChute
For PowerChute Serial Shutdown versions 1.5 and 1.6 on Linux
- Download the attached log4j-2.26.1.tar file, and if needed, copy the file to the Linux system.
- Uncompress the file. The command is tar -xvf log4j-2.26.1.tar.
- Stop the PowerChute service. The command is systemctl stop PBEAgent
- Change directory to where PowerChute has been installed. The default path is /opt/APC/PowerChuteSerialShutdown/Agent/
- Move the current log4j files. If PowerChute was installed to the default path, the command is mv /opt/APC/PowerChuteSerialShutdown/Agent/lib/log4j* /opt/APC
- Change directory to the log4j-2.26.1 directory that was created when log4-2.26.1.tar was uncompressed.
- Copy the new logj4 files to the PowerChute lib directory. If PowerChute was installed to the default path, the command is cp log4j.* /opt/APC/PowerChuteSerialShutdown/Agent/lib
- Restart the PowerChute service. The command is systemctl start PBEAgent
Опубліковано для: Schneider Electric Україна
Вкладення
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.