How can we help you today?
What is the contact rating of the 9999SX11 and 9999SX12?
Issue:
Where can I find the contact rating of part #s 9999SX11 and 9999SX12.
Product Line:
8502 Contactors and 8536 Starters
Environment:
NEMA Contactors and Starters
Resolution:
These contacts are designed for AC applications only. The following ratings are based on 35% power factor and voltage specific.
120 volts or less = 30 amp make, 3 amp continuous, 3 amp break.
120 to 600 volts = 3600 VA make, 3 amp continuous, 360 VA break.
Where can I find the contact rating of part #s 9999SX11 and 9999SX12.
Product Line:
8502 Contactors and 8536 Starters
Environment:
NEMA Contactors and Starters
Resolution:
These contacts are designed for AC applications only. The following ratings are based on 35% power factor and voltage specific.
120 volts or less = 30 amp make, 3 amp continuous, 3 amp break.
120 to 600 volts = 3600 VA make, 3 amp continuous, 360 VA break.
Released for: Schneider Electric UK
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.