How can we help you today?

Video: How do the ATV31/ATV312 logic inputs work when the VFD is in SINK mode?

Issue:
Programming and wiring logic inputs in SINK mode on Altivar 312 or Altivar 31 (ATV312/ATV31) Variable Frequency Drives (VFD).

Product Line:
ATV31 and ATV312

Environment:
All model

Cause:
Developing control scheme

Resolution:
The VFD is in sink mode when the control board DIP switch is in the SINK position.

Internally, the sinking mode connects the logic inputs to the +24V as the common.  A logic input is turned on by connecting it to the COM by means of a dry contact.

Note: When the logic inputs are configured for sink logic, grounding an input signal can result in unintended activation of drive controller functions.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings