Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What is the significance of the LA6DK10 footnote ``Does not include internal coil clearing contact.``?
Issue:
Detail about LA6DK10

Product Line:
Tesys D Contactors

Envinronment:
Accessories LA6DK10 LA6DK20 LAD6K10

Resolution:
Most mechanically held contactors are provided with a coil clearing contact so the coil does not remain energized, otherwise it would hum. In this device, a coil clearing contact needs to be added.  The coil is not rated for continuous duty, so keeping the latch block coil energized will burn up the coil. A normally open auxiliary contact can be wired in series with the unlatch coil to achieve coil clearing.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings