What is needed to interlock two LC1D80 or two LC1D95 contactors for a reversing application?
Issue:
Mechanical and electrical interlock for LC1D80** and LC1D95**
Product Line:
Tesys D line Contactors
Environment:
Contactor Accessories
Resolution:
For LC1D80 or LC1D95 with AC coils
LA9D4002 mechanical interlock with integral electrical interlocking
LA9D50978 mechanical interlock without electrical interlocking
LA9D8069 - 3 pole power connectors***
For LC1D80 or LC1D95 with DC coils
LA9D8002 mechanical interlock with integral electrical interlocking
LA9D80978 mechanical interlock without electrical interlocking
LA9D8069 - 3 pole power connectors***
***Connectors for 4 pole contactor set is LA9D8070.
Mechanical and electrical interlock for LC1D80** and LC1D95**
Product Line:
Tesys D line Contactors
Environment:
Contactor Accessories
Resolution:
For LC1D80 or LC1D95 with AC coils
LA9D4002 mechanical interlock with integral electrical interlocking
LA9D50978 mechanical interlock without electrical interlocking
LA9D8069 - 3 pole power connectors***
For LC1D80 or LC1D95 with DC coils
LA9D8002 mechanical interlock with integral electrical interlocking
LA9D80978 mechanical interlock without electrical interlocking
LA9D8069 - 3 pole power connectors***
***Connectors for 4 pole contactor set is LA9D8070.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.