How can we help you today?
Can a neutral terminal be used as an equipment ground terminal?
Issue:
Using QO and Homeline Load centers can the ground bar be used with neutral wires?
Product Line:
QO and Homeline Load Center
Environment:
Wiring
Cause:
Clarification
Resolution:
Sharing neutrals with grounds and visa versa, depends upon the application in which the load center is used.
If the load center is installed as the point of Service Entrance, the neutral is field bonded to the enclosure so any unused neutral / ground terminals may be used to terminate either wires. They are already commonly connected as the Service Entrance wiring standards dictate for load centers and panelboards.
If the load center is installed as a sub-panel, the neutral is isolated and not bonded to the enclosure's ground therefore all branch ground wires must be terminated into an equipment ground bar and neutrals to the neutral bar only.
Using QO and Homeline Load centers can the ground bar be used with neutral wires?
Product Line:
QO and Homeline Load Center
Environment:
Wiring
Cause:
Clarification
Resolution:
Sharing neutrals with grounds and visa versa, depends upon the application in which the load center is used.
If the load center is installed as the point of Service Entrance, the neutral is field bonded to the enclosure so any unused neutral / ground terminals may be used to terminate either wires. They are already commonly connected as the Service Entrance wiring standards dictate for load centers and panelboards.
If the load center is installed as a sub-panel, the neutral is isolated and not bonded to the enclosure's ground therefore all branch ground wires must be terminated into an equipment ground bar and neutrals to the neutral bar only.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.