How many LV cables can be connected to the phase and neutral terminals of Distribution Transformer?

The Fast Trans range of transformers which are liquid filled free breathing distribution transformers covers following kVA ratings and the number of Low Voltage cables that can be connected within the LV cable box varies for each rating as detailed below :-

See attached pdf files for aluminum and copper windings.


315kVA     One single core cable per phase and one on the neutral ( 4 single core cables total)

500kVA     One single core cable per phase and one on the neutral ( 4 single core cables total)

800kVA     Two single core cables per phase and two on the neutral ( 8 single core cables total)

1000kVA   Two single core cables per phase and two on the neutral ( 8 single core cables total)

1250kVA    Two single core cables per phase and two on the neutral ( 8 single core cables total)

1500kVA    Three single core cables per phase and three on the neutral ( 12 single core cables total)

2000kVA    Four single core cables per phase and four on the neutral ( 16 single core cables total)

The above number of LV cables are the standard arrangement. If alternative cable arrangements be required this should be discussed at the time of transformer tendering.

Schneider Electric UK

Attachment(s)
ECO Tier 2 Copper Fast Trans - Typical Customer Spec Issue 1 25-2-2021.pdf [145.45 KB]
ECO Tier 2_Aluminium Fast Trans - Typical Customer Spec_Issue 1_25-2-2021_EN.pdf [145.27 KB]
Explore more
Range:
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Category:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings