How many LV cables can be connected to the phase and neutral terminals of Distribution Transformer?
The Fast Trans range of transformers which are liquid filled free breathing distribution transformers covers following kVA ratings and the number of Low Voltage cables that can be connected within the LV cable box varies for each rating as detailed below :-
See attached pdf files for aluminum and copper windings.
315kVA One single core cable per phase and one on the neutral ( 4 single core cables total)
500kVA One single core cable per phase and one on the neutral ( 4 single core cables total)
800kVA Two single core cables per phase and two on the neutral ( 8 single core cables total)
1000kVA Two single core cables per phase and two on the neutral ( 8 single core cables total)
1250kVA Two single core cables per phase and two on the neutral ( 8 single core cables total)
1500kVA Three single core cables per phase and three on the neutral ( 12 single core cables total)
2000kVA Four single core cables per phase and four on the neutral ( 16 single core cables total)
The above number of LV cables are the standard arrangement. If alternative cable arrangements be required this should be discussed at the time of transformer tendering.
Released for: Schneider Electric UK
Attachment(s)
Explore more
Range:
Category:
Explore more
Range:
Category:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.