What are the percentage impedance guarantees of the Distribution Transformers?

The Fast Trans range of transformers, which are liquid filled free breathing distribution transformers, covers following kVA ratings and the percentage impedance guarantees for each rating as detailed below :-
See attached pdf references for both copper and aluminum windings.

315kVA           Percentage impedance guarantee = 4.75% at a Reference Temperature of 75ºC, subject to IEC 60076 Tolerances of ±10%
500kVA           Percentage impedance guarantee = 4.75% at a Reference Temperature of 75ºC, subject to IEC 60076 Tolerances of ±10%
800kVA           Percentage impedance guarantee = 4.75% at a Reference Temperature of 75ºC, subject to IEC 60076 Tolerances of ±10%
1000kVA         Percentage impedance guarantee = 4.75% at a Reference Temperature of 75ºC, subject to IEC 60076 Tolerances of ±10%
1250kVA         Percentage impedance guarantee = 5.0% at a Reference Temperature of 75ºC, subject to IEC 60076 Tolerances of ±10%
1500kVA         Percentage impedance guarantee = 5.5% at a Reference Temperature of 75ºC, subject to IEC 60076 Tolerances of ±10%
2000kVA         Percentage impedance guarantee = 6.0% at a Reference Temperature of 75ºC, subject to IEC 60076 Tolerances of ±10%

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.