Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What is the total heat loss of a Liquid Filled (Insulation Class "A") Power Distribution Transformer at various percentage loads?

The total heat loss of a Liquid Filled (Insulation Class "A") Power Distribution Transformer at various loads is calculated as follows :

At 100% load the total heat loss is the addition of the No Load Loss and the Load Loss

At X% load, the total heat loss is (X/100)² x Load Loss at 100% Load + No Load Loss

i.e. The No Load Loss is a constant loss and does not change with load
The Load Loss varies to the square of the per unit load

e.g. 1000kVA transformer with a No Load Loss of 1340 Watts and a Load Loss of 12500 Watts at 100% load and reference temperature of 75ºC, has the following losses at various loads

  • 100% Load       No Load Loss = 1340 Watts      Load Loss = (100/100)² x 12500 = 12500 Watts
  • 90% Load         No Load Loss = 1340 Watts      Load Loss = (90/100)² x 12500 = 10125 Watts
  • 80% Load         No Load Loss = 1340 Watts      Load Loss = (80/100)² x 12500 = 8000 Watts
  • 70% Load         No Load Loss = 1340 Watts      Load Loss = (70/100)² x 12500 = 6125 Watts
  • 60% Load         No Load Loss = 1340 Watts      Load Loss = (60/100)² x 12500 = 4500 Watts
  • 50% Load         No Load Loss = 1340 Watts      Load Loss = (50/100)² x 12500 = 3125 Watts

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings