How do I pass the wire through the CT's to give the right inputs to the LUTM?

If the Schneider Electric CT's are used the following table and diagram show how the power cables should be placed.

Please note - the LUTC CTs are now obsolete, alternatives have been advised where available.

Motor InPrimary (A)Secondary (A)No. of Pass(es)Old ReferenceNew Reference
3.5 to 10.53013LUTC0301N/A
5.2 to 163012LUTC0301N/A
10.5 to 323011LUTC0301N/A
17.5 to 535011LUTC0501N/A
35 to 10510011LUTC1001LT6CT1001
70 to 21020011LUTC2001LT6CT2001
140 to 42040011LUTC4001LT6CT4001
280 to 84080011LUTC8001LT6CT8001



CT loops