How do I wire the current transformers (cts) for a Tesys T, LUTM motor starter?

If the Schneider Electric CT's are used the following table and diagram show how the power cables should be placed.

Please note - the LUTC CTs are now obsolete, alternatives have been advised where available.

Motor InPrimary (A)Secondary (A)No. of Pass(es)Old ReferenceNew Reference
3.5 to 10.53013LUTC0301N/A
5.2 to 163012LUTC0301N/A
10.5 to 323011LUTC0301N/A
17.5 to 535011LUTC0501N/A
35 to 10510011LUTC1001LT6CT1001
70 to 21020011LUTC2001LT6CT2001
140 to 42040011LUTC4001LT6CT4001
280 to 84080011LUTC8001LT6CT8001