Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What are the separate parts required to build up star delta starters for motors 7.5kW through to 132kW suitable for mounting on DIN rail?

The table below indicates the selection of the power switching components necessary to build up a star delta starters, with mechanical interlocks between star and delta contactors, suitable for mounting on DIN rail in a suitable control panel.

Notes:

  • In some cases, the starter can be supplied assembled (prefix LC3) with the overload relay supplied separately. These should be checked on a case-by-case basis, as some are obsolete.
  • Overload selection is based on the motor full load current (FLC) x 0.58 due to the mounting position in the 'delta loop'.
  • In the case of 110 and 132 kW there is a requirement for a separate control relay and timer to ensure sufficient delay in the changeover time from star to delta contactor.

Motor FLC against power at 415V AC based on average typical motors

Complete Starters (Including Interlock)

Star Delta Starter components for customer assembly

Note: Star Delta Kit includes timer, power connections and mechanical interlock

Overload Selection

kW at 415V AC

Motor FLC (A)

Starter Plate Mounted

Line Contactor

Delta Contactor

Star Contactor

Star Delta Kit

Overload current (A) (FLC * 0.58)

Overload Class 10A (Adjustment range shown in brackets)

7.5

14

LC3D09A••

LC1D09***

LC1D09***

LC1D09***

LAD91217

8

LRD14 (7-10A)

11

21

LC3D12A••

LC1D18***

LC1D12***

LC1D09***

LAD91217

12

LRD16 (9-13A)

22

40

LC3D18A••

LC1D25***

LC1D25***

LC1D09***

LAD93217

23

LRD22 (16-24A)

30

55

LC3D32A••

LC1D32***

LC1D32***

LC1D18***

LAD93217

32

LRD35 (30-38A)

37

66

Not Available

LC1D40A***

LC1D40A***

LC1D40A***

LAD9SD3

38

LRD340 (30-40A)

55

100

Not Available

LC1D50A***

LC1D50A***

LC1D40A***

LAD9SD3

58

LRD365 (48-65A)

75

135

LC3D80••A64

LC1D80**

LC1D80**

LC1D80**

LA9D8018

78

LRD3363 (63-80A)

110

200

LC3D115••A64

LC1D115A***

LC1D115A***

LC1D115A***

LAD9150SD19 busbars

LAD5CM interlock

LADT2 timer

LADN11 aux for star contactor

CAD32•• control relay

116

LRD4367 (95-120A)

132

240

Not Available

LC1D150A***

LC1D150A***

LC1D150A***

139

LRD4369 (110-140A)

Replace *** with the following codes for coil voltage:

BNE - 24-60V AC/DC
EHE - 48-130V AC/DC
KUE - 100-250V AC/DC
LSE - 200-500V AC/DC (Only for LC1D115A & LC1D150A - For 415V AC on other contactors use 'N7')

Replace •• with the following codes for coil voltage:

B7 - 24V AC
F7 - 110V AC
P7 - 230V AC
U7 - 240V AC
N7 - 415V AC

There is a link below to our Coordination & Standards guide, this contains various Type 1 and Type 2 coordination tables for both star delta & direct online (DOL) starters along with other information on selecting contactors for various uses.

TeSys - Chapter A5 - Circuit breaker + contactor coordination tables and design guidelines - Digicat | Schneider Electric

The below drawing is an example of how a star delta starter power circuit and control circuit could look:
Star Delta drawing

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings