What is the maximum earth loop impedance values (Zs) for the GV4 range?

The charts below detail the Earth Loop impedance (Zs) for the GV4 range for any TN system based on the British Standard BS7671:2008+A3:2015

Two documents are also attached:
1) Sheet with Zs charts of TeSys motor circuit breakers:

  • TeSys GV2
  • TeSys GV3
  • TeSys GV4
  • TeSys GV7
  • TeSys U

2) Explanation of the calculation of the maximum Earth Loop Impedance

This also includes additional information about:
  • Motor Rated devices
  • Ambient Temperature

TeSys GV4 Range
Please refer to the charts below that detail the maximum earth loop impedance Zs for 0.4s disconnection time with Uo 230V

GV4L
ReferenceThermal Adjustment
Range In
Magnetic Tripping Current ImTolerance
Im+20%
Maximum Loop
Impedance Zs
(A)(A)(A)(Ω)
GV4LE02N212 .. 2833.606.50
GV4LE02S
GV4L02N
GV4LE03N3.521 .. 4958.803.72
GV4LE03S
GV4L03N
GV4LE07N742 .. 98117.601.86
GV4L07N
GV4LE07S
GV4LE12N12.575 .. 175210.001.04
GV4LE12S
GV4L12N
GV4LE25B25150 .. 350420.00.52
GV4L25B
GV4LE25N
GV4LE25S
GV4L25N
GV4LE50B50300 .. 7008400.26
GV4LE50N
GV4LE50S
GV4L50B
GV4L50N
GV4LE80B80480 .. 112013440.16
GV4LE80N
GV4LE80S
GV4L80B
GV4L80N
GV4L80S
GV4LE115B115690 .. 161019320.11
GV4LE115N
GV4LE115S
GV4L115B
GV4L115N
GV4L115S

GV4P
ReferenceThermal Adjustment
Range In
Magnetic Tripping Current ImTolerance
Im+20%
Maximum Loop
Impedance Zs
(A)(A)(A)(Ω)
GV4PE02N0.8 .. 23440.805.36
GV4PE02S
GV4P02N
GV4PEM02N
GV4PEM02S
GV4PE03N1.4 .. 3.56072.003.03
GV4PE03S
GV4P03N
GV4PEM03N
GV4PEM03S
GV4PE07N2.9 .. 7119142.801.53
GV4PE07S
GV4P07N
GV4PEM07N
GV4PEM07S
GV4PE12N5 .. 12.5213255.60.85
GV4PE12S
GV4P12N
GV4PEM12N
GV4PEM12S
GV4PE25B10 .. 254255100.43
GV4PE25N
GV4PE25S
GV4P25B
GV4P25N
GV4PEM25B
GV4PEM25N
GV4PEM25S
GV4PE50B20 .. 5085010200.21
GV4PE50N
GV4PE50S
GV4P50B
GV4P50N
GV4PEM50B
GV4PEM50N
GV4PEM50S
GV4PE80B40 .. 80136016320.13
GV4PE80N
GV4PE80S
GV4P80B
GV4P80N
GV4P80S
GV4PEM80B
GV4PEM80N
GV4PEM80S
GV4PE115B65 .. 115195523460.09
GV4PE115N
GV4PE115S
GV4P115B
GV4P115N
GV4P115S
GV4PEM115B
GV4PEM115N

Schneider Electric UK

Attachment(s)

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.