What is the heat/power dissipation on the LRD range of overloads?

Article available in these languages: Dutch

Please see the table below for heat/power dissipation on the LRD range of overload relays. For heat dissipation on the LRD overload relays with Everlink terminals, please see FAQ000233560.
Reference
Setting range (A)
Power dissipated in
VA at Ith max.
LRD01
0.1-0.16
1.33
LRD02
0.16-0.25
1.4
LRD03
0.25-0.40
1.38
LRD04
0.40-0.63
1.24
LRD05
0.63-1
1.55
LRD06
1-1.6
1.61
LRD07
1.6-2.5
1.67
LRD08
2.5-4
1.61
LRD10
4-6
2.14
LRD12
5.5-8
1.83
LRD14
7-10
1.77
LRD16
9-13
2.42
LRD21
12-18
1.99
LRD22
16-24
2.53
LRD32
23-32
2.43
LRD35
30-38
3.04
LRD3322
17-25
3.42
LRD3353
23-32
3.81
LRD3355
30-40
4.52
LRD3357
37-50
6
LRD3359
48-65
7.98
LRD3361
55-70
8.18
LRD3363
63-80
10.17
LRD3365
80-104
5.62
LRD4365
80-104
6.7
LRD4367
95-120
8.35
LRD4369
110-140
10.38
LRD33656
80-104
7.57
LRD33676
95-120
9.5
LRD33696
110-140
11.95

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings