Will the GV ranges of MPCB get de-rated with altitude? How will the de-rating work?
Please note - the GV7 range is now obsolete, the data on this range is now for reference only.
For GV2, GV3 and GV7:
Yes, for altitudes higher than 2000m, see the de-rating on this table below:
For GV4, GV5 and GV6:
Yes, for altitudes higher than 2000m, see the de-rating on this table below:
For GV2, GV3 and GV7:
Yes, for altitudes higher than 2000m, see the de-rating on this table below:
| Altitude | Ue | Ie |
| ≤ 2000m | 1 (no de-rating) | 1 (no de-rating) |
| 2500 m | 0.9 | 0.92 |
| 3000 m | 0.8 | 0.90 |
| 3500 m | 0.7 | 0.88 |
| 4000 m | 0.6 | 0.86 |
For GV4, GV5 and GV6:
Yes, for altitudes higher than 2000m, see the de-rating on this table below: