How can we help you today?

What derating factors are applied to Tesys K, D, G contactors at altitude?

For contactors in the TeSys ranges (K, D & G) Please apply the following:

No derating below 3000m altitude for voltage and current in the power poles of the contactors.

Derating table for Tesys D contactors

For example, a LC1D80 at 5000m :

  • The maximum rated operational voltage is 1000V (IEC 947-4) and 690V (UL/CSA). At 5000m it becomes 1000V x 0.6 = 600V (IEC 947-4) and 690V x 0.6 = 414V (UL/CSA).
  • The maximum rated operational AC3 current is 80A at 5000m becomes 80A x 0.86 = 68A.

Schneider Electric UK

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.