Does Schneider Electric offer contactors with N/C (normally closed) main poles?

Occasionally, there is a requirement for contactors with all or some of the main power poles in the normally closed (N/C) configuration.

Due to the rarity of applications that require N/C main poles, and the technical challenge that designing a contactor with N/C poles poses, there is a smaller choice of products available in this format.

Products available from the Schneider Electric TeSys contactor range with some or all of the contacts N/C;

  • TeSys D contactors with the following part number format have 2 normally open (N/O) and 2 N/C main poles; LC1D**8** - AC-1 duty only
    Example part number; LC1D128F7 specification; 2 N/O and 2 N/C main poles, rated 25A AC1 duty, 1 N/O + 1N/C auxiliary contacts, 110V ac coil.
  • TeSys GC Modular contactors. These contactors are available in a variety of pole compositions including 1, 2,3 or 4 N/C and also in versions with both N/O and N/C poles. Maximum current rating with N/C poles is 63A AC-7a duty only.
    Example part number; GC6304M5 specification; 4 N/C main poles, rated 63A AC-7a duty, 220 / 240 V 50Hz ac coil.
  • CV1 / CV3 variable composition 'bar and shaft' contactors. These contactors were custom built to order but unfortunately they are not available from Schneider Electric anymore. This particular range was sold to Lenoir Elect (https://www.lenoir-elec.com) so you can still get this particular offer from them.


#Note: To obtain further information on the first two options given above, click on the range links to the right or search in our website.

If a suitable N/C contactor cannot be sourced, there are some options you can consider. Suitability will depend on the application and would need to be verified by the electrical engineer responsible for the project;

  • Use of a standard contactor with N/O  main poles held closed by the contactor coil*. This does not, however, address a requirement for the main poles to close on loss of a control supply.
  • Use of a standard contactor with N/O main poles held closed by a mechanical latch block. This solution requires the contactor to be energised conventionally via it's coil circuit, which closes the main contacts. Once closed the coil circuit is removed and the contactor remains closed by means of a mechanical latching mechanism. To open the contactor contacts, the mechanical latch block has another 'de-latch' coil. Again, this does not address a requirement for the main poles to close on loss of a control supply.

*Note: It is perfectly acceptable to energise a contactor coil for long periods providing precautions are taken (Observe all catalogue and data sheet performance limits, particularly temperature and voltage limits, periodically cycle test the contactor by de-energising and re-energising the coil circuit).

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings