Power Consumption of APC Rack Power Distribution Unit (PDU) / Automatic Transfer Switch (ATS) Products
| Rack Power Distribution Unit (PDU) Type | Total Power Consumption (no outlets "ON") | Wattage Draw Per "ON" Outlet | Total Power Consumption (all outlets "ON" - assuming up to 24 outlets) |
|
| N/A | N/A | approx. 5 watts |
Metering By Outlet (MBO) (AP84XX) | N/A | N/A | approx. 11.5 watts |
|
| N/A | N/A | 5 watts |
|
| approx. 5 watts | approx. 1 watt | approx. 29 watts |
|
| 5 watts | .5 watts | 17 watts |
|
| 18 watts | .25 watts | 24 watts |
| Netshelter Rack PDU Advanced Switched, and Switched with Outlet Metering (APDU10XXXSW/APDU10XXXSM) | ~6 watts | C13 Outlet: 0.3 watts C19 Outlet: 0.5 watts | Metered and switched by outlet, 48 outlets on, NMC with dual ethernet and with two physical sensors = ~23.2W. Metered and switched by outlet, 12 C13 and 12 C19 outlets on, NMC with dual ethernet and with two physical sensors = ~16W. |
|
| Total Power Consumption (no outlets "ON") | Wattage Draw Per "ON" Outlet | Total Power Consumption (all outlets "ON") |
|
| N/A | N/A | approx. 20 watts |
| All models (AP44XX) | N/A | N/A | < 20 watts |
Note: These measurements don't include resistive losses due to current flow through the Rack PDU or Rack ATS meaning, they are only the fixed losses of the PDU or ATS associated with communications, measurements, and relay control.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.