How can we help you today?
Single Phase Symmetra XR Battery frame displays EF or E1
Issue
XR frame displays E1 or EF. The mainframe indicates that an XR frame fault exists.
Product Line
Symmetra Power Array
Symmetra RM
Symmetra LX
Single Phase Symmetra XR Frames
Environment
All serial ranges
Cause
This error indicates that the XR communication card (either SYXRCC or SYAFSU16) located in the XR frame has experienced an internal problem.
Resolution
The card will need to be reseated. If reseating does not clear the fault, the card must be replaced.
For instructions on reseating the card please refer to FA157406
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.