Video: What does a flashing E on the ATV212 or ATV21 display (External Fault on the graphic keypad) mean?
Issue:
What does a blinking E on the ATV21 or ATV212 display mean?
What does External Fault mean on the graphic keypad?
Product Line:
Altivar 21
ATV21
Altivar 212
ATV212
S-flex enclosed ATV21/ATV212
Environment:
All
Cause:
Flashing E on the display of the ATV21 or ATV212 drive.
Resolution:
The drive is in a faulted status, initiated by one of the following:
1) CMOd is set to 0 or 2, the drive is in remote mode and the keypad STOP button is pressed. Since the drive is looking for a stop command from a logic input or serial communications, the STOP button is assigned to function as an E-STOP. (See page 87 in the ATV212 Programming Manual and attachment)
2) A logic input is assigned as External Fault, functions 11 or 45, and that logic input fault is activated.
To reset the fault, either cycle power to the drive or activate a logic input that is assign as Fault Reset, functions 10 or 55.
Video uses the ATV212 drive for demonstration purposes:
What does a blinking E on the ATV21 or ATV212 display mean?
What does External Fault mean on the graphic keypad?
Product Line:
Altivar 21
ATV21
Altivar 212
ATV212
S-flex enclosed ATV21/ATV212
Environment:
All
Cause:
Flashing E on the display of the ATV21 or ATV212 drive.
Resolution:
The drive is in a faulted status, initiated by one of the following:
1) CMOd is set to 0 or 2, the drive is in remote mode and the keypad STOP button is pressed. Since the drive is looking for a stop command from a logic input or serial communications, the STOP button is assigned to function as an E-STOP. (See page 87 in the ATV212 Programming Manual and attachment)
2) A logic input is assigned as External Fault, functions 11 or 45, and that logic input fault is activated.
Check the following parameters:
F111 - Terminal F logic input assignment (default = 2; run forward)
F112 - Terminal R logic input assignment (default = 6; preset speed)
F113 - Terminal RES logic input assignment (default = 10; fault reset)
F111 - Terminal F logic input assignment (default = 2; run forward)
F112 - Terminal R logic input assignment (default = 6; preset speed)
F113 - Terminal RES logic input assignment (default = 10; fault reset)
To reset the fault, either cycle power to the drive or activate a logic input that is assign as Fault Reset, functions 10 or 55.
Video uses the ATV212 drive for demonstration purposes:
Released for: Schneider Electric UK
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.