Is it acceptable to use three separate single-phase MCBs (one per phase) on a three-phase supply, or must a three-phase MCB be used instead?

It is possible to fit single phase breakers in a three phase distribution board. However, it is not good practice to have 3 single phase breakers on a three phase circuit for these reasons:

  • Damage to Motors - Motor loads or circuits that are critical to have three phase voltage may be damaged by the loss of one phase. This is often called "Single Phasing".
  • Danger to personnel - Someone working on the installation may assume that the fault on a three phase load has disconnected all three phases, but two are still connected
  • Danger to equipment - The fault was caused by a problem with the installation, therefore it would be good to disconnect the load from the three phase device

However using 3 x single pole devices would be similar to the protection offered by a fuse and fuse carrier.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings