How can we help you today?

How to wire start stop on the ATV61 or ATV71 drives?

Issue:
Wiring a start stop pushbutton or a dry contact on ATV61 or ATV71.

Product line:
ATV61 and ATV71

Environment:
All models, all serial numbers

Cause:
Wiring

Resolution:
In 2-wire control, wire the start/stop contact between +24 and L11.
In 3-wire control, the normally closed Stop pushbutton is wired between +24 and LI1. The normally open Start pushbutton is wired between +24 and LI2.

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.