Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Where can I find basic programming information for ATV32?

Issue:
Looking for basic programming information for ATV32

Product Line:
Altivar ATV32

Environment:
All

Cause:
Programming configuration set up

Resolution:

CONF>FULL>SIM

bFr= Base motor frequency 60hz
nPr= HP of he motor
UnS= Rated motor voltage
nCr= Rated motor current (motor FLA)
FrS= Rated motor frequency
nSP= Ratd motor speed (rpm's on motor nameplate)
tFr= Max frequency
ItH= Motor thermal current (match motor FLA)
ACC= Acceleration (ramp up) time
dEC= Deceleration (ramp down) time
LSP= Low speed
HSP= High speed

Schneider Electric UK

Attachment(s)
ATV32 Programming Manual.pdf [3.38 MB]
ATV32 quick start guide.pdf [1003.56 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings