Load (PC to Sepam) and Upload (Sepam to PC) options are greyed out in SFT2841 when connected to a Sepam relay
Issue
Why are the Load and Unload (Upload) options greyed out in SFT2841 when attempting to transfer settings files to or from a Sepam relay?
Product
Sepam 20, Sepam 40, Sepam 80, SFT2841
Environment
- Sepam relay configuration using SFT2841
- Windows-based PC connected to Sepam relay
Cause
The Load and Upload options are disabled due to missing prerequisites:
- For Sepam 20, the configuration password has not been entered.
- For Sepam 40 and 80, there is no active connection to the relay.
Additionally, opening a settings file before establishing a connection (for Sepam 40/80) prevents the options from becoming available.
Resolution
Sepam 20 Series Relay:
- Open SFT2841.
- Click the key icon in the upper-left corner.
- Enter the password (default: 0000).
- Once authenticated, go to Sepam > Load or Sepam > Upload.
Sepam 40 and 80 Series Relays:
- Ensure SFT2841 is closed if a file is already open.
- Open SFT2841 and establish an active connection to the relay.
- Do not open the settings file beforehand.
- Once connected, navigate to Sepam > Load or Sepam > Upload.
Note:
- Only Sepam 20 requires password authentication before enabling Load/Upload.
- NSepam 40 and 80 require an active relay connection instead.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.