How can we help you today?

View Angle of Magelis XBTG Series

Goals and Symptoms

View Angle of Magelis XBTG Series

Facts and Changes

View Angle

Causes and Fixes


Up/Down/Left/Right
XBTG2120 ---> 20/30/30/30
XBTG2130 ---> 20/30/30/30
XBTG2220 ---> 35/40/55/55
XBTG2330 ---> 65/40/65/65
XBTG4320 ---> 30/60/55/55
XBTG4330 ---> 30/60/55/55
XBTG5230 ---> 25/15/30/30
XBTG5330 ---> 35/55/60/60
XBTG6330 ---> 45/50/60/60

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.