Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Can I automatically backup my Alarm Summary page in Vijeo Designer?

Yes. In Vijeo-Designer, the alarm information (from all 3 types of alarm databases: Active, History and Log) can be backed up to the SRAM so that it is not lost when a power outage occurs. To do this, click "Alarms" in the Navigator and set the "Backup Alarm Group" property to "Yes".
image1


image2

When Backup Alarm Group = Yes in the Alarms node properties, the Num Of History Alarms and Num Of Log Alarms in the alarm group properties, plus the number of variable alarms, define how many alarms are backed up to SRAM.
Backup Alarms = History + Log + Active

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings