Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How do I read or write a program to/from the SY/MAX model 50 controller to the 8005PR4 hand held programmer?

Issue

How do you I read or write a program to/from SY/MAX model 50 controller to the 8005PR4 hand held programmer?

Product Line

SY/MAX

Environment

80005PR4

Resolution

To read a program from the SY/MAX model 50 controller to the 8005PR4 enter the following sequence:

  1. TRS, READ.
  2. Once "TRS P T L GO?" is displayed make sure the CPU is halted and a memory pack is installed and then press the ENTR key. "TRS P T L" is displayed during execution.
  3. When completed "TRS P T L END" is displayed.


To write a program from the 8005PR4 to the SY/MAX model 50 controller enter the following sequence:

  1. TRS, ENTR.
  2. Once "TRS L T P GO?" is displayed make sure the CPU is halted and either a 8005MP1 or 8005MP4 CMOS RAM memory pack is installed and then press the ENTR key. "TRS L T P" is displayed during execution.
  3. When completed "TRS L T P END" is displayed.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings