How can we help you today?

Why do I get error 79 from SYMATE PLUS when I try to insert rungs into my running SYMAX controller from online?

Issue

Why do I get error 79 from SYMATE PLUS when I try to insert rungs into my running SY/MAX controller from online?

Product Line

SY/MAX

Environment

SYMATE Plus

Resolution

This is due to the program using timed interrupts. As timed interrupts could not be guaranteed to be maintained during insertion, the operation is not allowed while the controller is in RUN mode. You will either need to do the operation off-line, or you need to halt the controller.

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.