Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Air flow for ATV78 from 200kw up to 710kw

Goals and Symptoms

What is the air flow of the fans necessary for the enclosure, in the catalog page 38, it appears up to 160kw, and what is needed is for powers from 200kw to 710kw high torque?

Causes and Fixes

From ATV 780C20Y to ATV 780C31Y -> air cooling: 2600m3/h
From ATV 780C35Y to ATV 780C50Y -> air cooling: 3900m3/h
From ATV 780C56Y to ATV 780C71Y -> air cooling: 5200m3/h

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings