How can we help you today?

Is the Modicon M340 platform rated for extended temperature ?

Issue:

Is the Modicon M340 platform rated for extended temperature ?

Product Line:

Modicon M340

Resolution:

There is a model of M340 built for harsh environments. It offers an extended temperature range of   (-13 to 158 F)
In order to obtain this extended temperature capability the M340 part number requires an "H" suffix. For example:  BMXP342020H.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.