What is the function of the Reset button on the Modicon M340 platform power supply modules ?

The Reset button of the M340 power supply modules, when pressed, simulates a power outage and launches a cold start of the application. In addition, all modules in the rack are power cycled, the alarm relay is forced open, and the OK LED is turned off.