Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How to change the Time and Date on a 174CEV20040 Modbus Plus to Ethernet Bridge?

Goals and Symptoms:

How to change the Time and Date on a 174CEV20040 Modbus Plus to Ethernet Bridge?

Causes and Fixes:


To change the Time and Date on a 174CEV20040 bridge it must be done in the Monitor Console Mode. To access the monitor console, you must plug a standard PC keyboard, a mouse, and a VGA monitor into the bridge connectors. The editing screen below shows the factory default settings. Initially all the controls will be grayed-out and the data field will be display-only. To operate the controls, click Login under Administrator Account, and enter the password. The default password is password. The controls are now active and Login changes to Logout.
To change the Time and Date, just press the pull down in the Troubleshooting Tools section and scroll down until you see the Time and Date selection then press the Run button. A Time and Date properties window will appear for you to make the changes, when finished press the OK button to exit that screen.


Note: After all changes have been made press the Reboot button for the system to reboot and all changes to take effect


Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings