How can we help you today?
How to configure the STBEHC3020 for one shot mode
Issue
How to configure the STBEHC3020 for one shot.
Product Line
All versions of the Advantys Configuration Software.
Environment
Windows 7
Resolution
Wire the 'STBEHC3020' to the incremental encoder.
- Double click on the 'STBEHC3020' module to open the properties window for the module.
- Configure the parameters as shown.
- Start the PLC.
- Set the Input Validation bits to Off.
- Enable the Counter Synch
- Enable the Counter Enable
To reset the counter, toggle the counter sync bit from 0 to 1.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.