Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
When you do not have a Modbus product, here is a step by step procedure to change the units in the REG24 from Deg. C to Deg. F.

Goals and Symptoms

When you do not have a Modbus product, here is a step by step procedure to change the units in the REG24 from Deg. C to Deg. F.

Facts and Changes

REG24
°C
°F
Configuration

Causes and Fixes

Originaly, the parameter to change the temperature units is not accesible from the front face.
So first, you have to allow the display of this parameter.
Steps to follow:
1.Press the key SEL until you display "P-n1".
2.Press "Down" arrow key until you display "dSP5".
3.Press SEL
4.Change the value from 212 to 208 with the "Down" arrow key.
5.Press SEL to exit the menu.

Now you can have acces to the parameter.
Steps to follow:
1.Press the key SEL until you display "P".
2.Press "Down" arrow key until you display "P-F"
3.Press SEL
4.Change the value from °C to °F with the arrow key.
5.Press SEL to exit the menu.


Legacy KB System (APS) Data: RESL201840 V1.0, Originally authored by LaBe on 04/01/2010, Last Edited by LaBe on 04/01/2010
Related ranges: Zelio Control

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings