Problem Viewing Momentum 170ENT11001 Web Page Applets. (600 Error access builtin CGI file)

Release Notice

The purpose of this Resolution is to inform users that a problem viewing web page applets from a Momentum 170ENT11001 Ethernet Communication adapter has been resolved.

Goals and Symptoms

Web browsers with Java versions 1.4.2_xx not installed do not properly display the 170ENT11001 web page applets. When trying to launch any page beyond the main page the following error will display. (600 error access builtin CGI file).

Facts and Changes

Installing SUN Java version of 1.4.2_14 into Windows browsers allows the 170ENT11001 web page applets to be viewed properly.

Causes and Fixes

Go to the SUN Java website http://www.oracle.com/technetwork/java/javasebusiness/downloads/java-archive-downloads-javase14-419411.htmlto download and run Java Runtime Environment (JRE) v1.4.2_14.


After installing and enabling this Java version in your PCs control panel the 170ENT11001 web page applets will display properly. Java control panel

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.