What does a Unity Quantum "Dead error 405 81" indicate?

Issue:

What does a Unity Quantum "Dead error 405 81" indicate?

Product Line:

Unity Quantum

Resolution:

Dead error 405 is defined as "time out waiting for Modbus Plus"
Sub code 81 means "Prom Checksum error"
During operation the MB+ processor (on the CPU) periodically performs self tests. This error means that the computed checksum was bad.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.