How can we help you today?

What is the Modubs Register for Digital Input 1 (DI1) for a 7650

Issue

What Modbus register should be used to read Digital Input 1 (DI1) on an ION7650 meter?

Product Line

PowerLogic ION7650

Environment

Modbus (RTU or TCP)

ION Setup or ION Designer

External SCADA/PLC/RTU

Cause

Not all ION modules have a hard‑coded Modbus register. DI1 on the ION7650 is one such case.

Resolution

  • Map the DI1 module’s State output to a Modbus Slave register, then read that Modbus holding register from your master.

Note

ION7650 is discontinued, the recommended Schneider Electric replacement  is ION9000 series.

Schneider Electric UK

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.