How to read energy registers from a CM2xxx series meter?
Issue
How to read energy registers from a CM2000 series meter?
Product Line
CM2000 series meter
Cause
Customer is having issues reading KWh via modbus registers
Environment
CM2000
Resolution
The CM2000 series energy is stored in 4 registers (except Incremental Energy, which is stored in 3 registers). These registers use the Modulo 10,000 format which uses the following formula:
R4*10,000^3 + R3*10,000^2 + R2*10,000 + R1
Details explaining Mod 10k as well as examples can be found in FA212766.
The CM2000 energy registers are listed below as a reference:
ACCUMULATED ENERGY
| 1601–1604 | Real Energy In 3-Phase Total (WH) | 0 to 9,999,999,999,999,999 |
| 1605–1608 | Reactive Energy In 3-Phase Total (VArH) | 0 to 9,999,999,999,999,999 |
| 1609–1612 | Real Energy Out 3-Phase Total (WH) | 0 to 9,999,999,999,999,999 |
| 1613–1616 | Reactive Energy Out 3-Phase Total (VArh) | 0 to 9,999,999,999,999,999 |
| 1617–1620 | Apparent Energy, 3-Phase Total (VAH) | 0 to 9,999,999,999,999,999 |
| 1621–1624 | Real Energy Signed/Absolute 3-Phase Total (WH) | 0 to ±9,999,999,999,999,999 |
| 1625–1628 | Reactive Energy Signed/Absolute 3-Phase Total (VArH) | 0 to ±9,999,999,999,999,999 |
CONDITIONAL ACCUMULATED ENERGY
| 1629–1632 | Conditional Real Energy In, 3-Phase Total (WH) | 0 to 9,999,999,999,999,999 |
| 1633–1636 | Conditional Reactive Energy In 3-Phase Total (VArH) | 0 to 9,999,999,999,999,999 |
| 1637–1640 | Conditional Real Energy Out, 3-Phase Total (WH) | 0 to 9,999,999,999,999,999 |
| 1641–1644 | Conditional Reactive Energy Out 3-Phase Total (VArH) | 0 to 9,999,999,999,999,999 |
| 1645–1648 | Conditional Apparent Energy 3-Phase Total (VAH) | 0 to 9,999,999,999,999,999 |
INCREMENTAL ACCUMULATED ENERGY
| 1649–1651 | Incremental Real Energy In, 3-Phase Total (WH) | 0 to 999,999,999,999 |
| 1652–1654 | Incremental Reactive Energy In 3-Phase Total (VArH) | 0 to 999,999,999,999 |
| 1655–1657 | Incremental Real Energy Out, 3-Phase Total (WH) | 0 to 999,999,999,999 |
| 1658–1660 | Incremental Reactive Energy Out 3-Phase Total (VArH) | 0 to 999,999,999,999 |
| 1661–1663 | Incremental Apparent Energy 3-Phase Total (VAH) | 0 to 999,999,999,999 |
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.