How can we help you today?
Connecting to an ION 7700 Meter using Modbus TCP
Goals and Symptoms
The ION 7700 inherently supports Modbus TCP through the Xpress Cards Ethernet port. The meter will recognize Modbus TCP communications if you configure the Ethernet ports Protocol setup register to Modbus RTU.
Causes and Fixes
Configure the ION 7700 to communicate Modbus TCP:
- 1. On the ION 7700 MGT, select Setup, Quick Setup, and then Ethernet COM.
2. Select ETH1 Protocol, and then enter the meter password when prompted.
3. Change the protocol from ION to Modbus RTU.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.