How can we help you today?

Does the Modbus Cradle Communication Module (CCM) support 2 wire RS485 communications?

Issue:
User may need to connect the CCM to a 2 wire daisy chain.

Product Line:
Cradle Communication Module

Environment:
RS-485 Communications

Resolution:
The Modbus Cradle Communications Module does support 2 wire RS485 communications. The module can be configured by jumpering the IN+ and the OUT+ and the IN- and the OUT-.

Schneider Electric UK

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.