How can we help you today?
Calibration standard for ION meters
Product Line
2. ANSI C12.20 Accuracy Class 0.2 or Class 0.5 at 25°C (77°F)
Specialized electrical testing EQUIPMENT is used to calibrate in production line. The procedure aims to calibrate the meters voltage, current and frequency. A meter type specific set of voltage, current, PF and frequency points are applied.
Document Change History
ION8800
ION8600
ION7650
ION7550
ION7350
ION7330
ION7300
ION6200
ION8600
ION7650
ION7550
ION7350
ION7330
ION7300
ION6200
Resolution
The calibration procedure followed for ION Meters (ION8800, ION8600, ION7650, ION7550, ION7350, ION7330, ION7300, ION6200) seeks to meet two standards:
2. ANSI C12.20 Accuracy Class 0.2 or Class 0.5 at 25°C (77°F)
Specialized electrical testing EQUIPMENT is used to calibrate in production line. The procedure aims to calibrate the meters voltage, current and frequency. A meter type specific set of voltage, current, PF and frequency points are applied.
Document Change History
| Date and Initials | Comments |
| 2010-11-19 DRM | * Added precision to include references to the "0.2 Accuracy Class" as this was not mentioned in the original version of this article. * Updated information on the version of the standards currently used (IEC 687 has been superceded by IEC 62053-22). * Eliminated all references to the range of current level employed in the testing sweeps of the conformance testing procedure since this is not relevant in the context of the level of detail of this article. * Eliminated references to the frequencies at which the conformance testing is conducted because the details are actually more complicated than simply 50 and 60 Hz. |
Released for: Schneider Electric UK
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.