How can we help you today?
The ION 75xx RTU reads -1 for all external numeric registers and will not save any changes after a register write
Issue
The ION 75xx RTU reads -1 for all external numeric registers and will not save any changes after a register write.
Product Line
ION7550 RTU
ION7500 RTU
Environment
ION Framework
Cause
The ION 75xx RTU units do not come with predefined framework on the meters. If a module does not exist on the framework, Modbus requests will return -1.
Resolution
Use ION Setup or ION Designer to create external numeric modules and unlock the registers. Once the module has been created the register will read 0 instead of -1.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.