Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What is the difference between an EGX100 and a TSXETG100?

Issue
What is the difference between an EGX100 and a TSXETG100?

Product Line
EGX100

Environment
Part number

Cause
Are different protocols supported between the EGX100 and TSXETG100?
Do the EGX100 and TSXETG100 support the same devices?

Resolution
The EGX100 is a Square D branded Ethernet gateway and the TSXETG100 is a Telemecanique branded Ethernet gateway. The units are physically the same, but offer different transmission modes for serial communications.
The EGX100 supports Modbus RTU, Jbus, PowerLogic (SY/MAX), and Modbus ASCII.
The TSXETG100 only supports Modbus RTU and Modbus ASCII. PowerLogic legacy devices such as CM100/200s and CM2000s, as well as SEPAM Relays, would be unable to communicate through a TSXETG100.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings