How can we help you today?
Can leakage voltage affect 7550/7650 digital inputs?
Issue
Can leakage voltage affect 7550/7650 digital inputs?
Product Line
ION7550, ION7650
Environment
Digital inputs on ION7550 and ION7650 meters connected to external triggering devices.
Resolution
Goals and Symptoms
In certain cases, a device connected to and triggering the digital inputs on an ION7650 or ION7550 can have a leakage voltage. A leakage voltage occurs when a device produces a small amount of voltage across its terminals when it is open (ideally, this should be 0 volts).
When the device closes the circuit, the digital input registers a trigger. When the device opens the circuit, the digital input should not register a trigger. However, if there is leakage voltage when the triggering device is open, testing is required to determine if the leakage is enough to falsely trigger the input.
Facts and Changes
- The internal resistance between Scom and S8 or S7 is 230 kΩ on meters manufactured after September 2009.
- On older 7550/7650 meters (before September 2009), the internal resistance was 40 kΩ.
- The minimum current required for the meter’s digital input to register a pulse is 50 microamperes (µA).
Causes and Fixes
If the leakage voltage across the digital input connection produces a current of 50 µA or more, the input may falsely register as closed.
To resolve this:
- Calculate the leakage current using Ohm’s law:
Current (A) = Leakage Voltage / Internal Resistance - If the current is ≥ 50 µA, modify the circuit to reduce the leakage current (e.g., by adding a resistor or using an isolation relay).
The minimum amount of current required for the meter at the digital inputs to register a pulse is 50 micro A.
Hence with this information, figure out if a leakage voltage across the digital input connection is enough to produce a 50 micro ampere current. If the leakage produces a 50 micro ampere current or more work out the circuit to reduce the current.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.