How does the counter module operate with a High Speed input on an ION meter?
The input to a counter module can be attached to a High Speed output module, and it will count the High Speed results. The output of the counter module, however, will only update once per second.
For example if the input is pulsing 12 time per second the output will be:
| Time (s) | Input pulses | Output Register of the Counter module |
| 0 | 0 | 0 |
| 1 | 0 | |
| 2 | 0 | |
| …. | 0 | |
| 1 | 12 | 12 |
| 13 | 12 | |
| 14 | 12 | |
| …. | 12 | |
| 2 | 24 | 24 |
| 25 | 24 | |
| 26 | 24 | |
| ….. | 24 |