In the EGX300, default channel names for BCPM, BCM, and Acti 9 Smartlink do not update to the Administrator user account's language
Goals and Symptoms
Symptoms
For BCPM, BCM, and Acti 9 Smartlink device types, if custom channel/circuit names have been applied, any default channel/circuit names do not update to the Administrator user account language if the language is changed after one of these devices is added.
This can be observed under Monitoring > Real Time Data > Single Device Pages for the mentioned device types.
Causes and Fixes
Cause
The Administrator user account language is changed after a user has applied changes to any channel/circuit names for the devices above. This occurs because a static configuration file is created after any changes are applied to the channel/circuit names.
Resolution
Follow the steps below to reset the default channel names to the Administrator user account language.
NOTE: The following steps will delete custom channel names, and you will have to re-enter any custom names afterward. Channel names are the only information that is reset.
- Launch Windows Explorer, type ftp:// and the IP address of the EGX in the Address text box, then press Enter.
- Enter the Administrator user name and password, then press Enter.
- Double-click the www folder to open it.
- Find the configuration file for the device. The format for the configuration file is [Device Name]_[Local ID].conf.
NOTE: To find the device's Local ID, go to the EGX300 Setup page and click on Device List. - Right-click on the .conf file, then click Delete.
- Click Yes to confirm file deletion.
Workaround
Apply custom names to all channels/circuits for these device types.
Legacy KB System (APS) Data: RESL210948 V1.0, Originally authored by MaTh on 03/13/2013, Last Edited by MaTh on 03/13/2013
Related ranges: EGX300
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.