How can we help you today?
What is the correct order to upgrade the exec in the Quantum Unity processor 140CPU651x0?
1. Processor Operating Systems are upward compatible: updating a processor with a higher Operating System version is always allowed
2. It is recommended to always upgrade the OS version of a processor with the latest available version
3. It is recommended that the Copro version is associated with the OS version indicated in the QUANTUM - Launch History tables (mandatory for HotStandby Systems)
4. It is mandatory to upgrade the Ethernet Coprocessor before the Processor OS
5. It is not recommended to downgrade the OS of a Processor
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.