Setting up a Write_Var command to have a M340 PLC write data directly to a supported TCP/IP device.

Follow the below procedure :

  1. Create an Ethernet I/O network — In your Unity Pro project, add a new Ethernet network, configure it for your application, and validate the changes.
  2. Link the network to the CPU's Ethernet port — In the hardware configuration, assign the network you just created to the CPU's built-in Ethernet port.
  3. Enable array entry in project settings — Go to Tools > Project Settings and check the data-type options that allow arrays to be entered directly, instead of having to declare them as variables first.project option
  4. Add an ADDM block — Set its IN parameter to the target device's IP address as a quoted string, in the form 'TCP_IP{x.x.x.x}' — quotation marks required on both sides since it's a character string.
  5. Add and wire a WRITE_VAR block — Connect the ADDM block's output to a WRITE_VAR (or READ_VAR) block to complete the data exchange with the target device.


Below an example with the NetLink id "Ethernet_1" and IP address of the device 192.168.40.11.
Next configure the remaining parameters of the Write_Var block where:

OBJ = String declaring the type of object to Write (%MW or %M)
NUM = The starting register address in the Slave device to were the data will be sent
NB = The # of registers to write
GEST = Array of length 4 where the Management Exchange table for the Write_Var is located
EMIS = Array of length NB where the Write data is stored in the M340.
Note: The Array's are of type INT if declared as variables.

WRITE_VAR , example


Finally build, download, and run the program

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.