How can we help you today?
What is the Syntax of the IN Parameter of the ADDM block used by M340 PLCs when communicating over Ethernet?
The ADDM function block builds a device address string for use with communication blocks like READ_VAR or WRITE_VAR.
The input parameter is:
For addressing a station over Ethernet, IN takes one of these forms:
'Netlink{hostAddr}''Netlink{hostAddr}TCP.MBS''Netlink{hostAddr}MBS''r.m.c{hostAddr}''r.m.c{hostAddr}TCP.MBS''r.m.c{hostAddr}MBS''Netlink{hostAddr}node'
Where:
Netlink— the network name set in the Net Link field of the Ethernet channelhostAddr— the IP address of the target devicer— rack numberm— module positionc— channel numbernode— the Modbus or CANopen node behind a gateway (the gateway itself is identified byhostAddr)MBS— Modbus ServerTCP.MBS— TCP Modbus Server
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.